Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/20/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
05/17/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) NO POWER TO OUTLETS IN THE DINING ROOM 2) OUTLET ON SOUTH WALL SOUTH OF SLIDING GLASS DOOR IN LIVING ROOM IS DEAD 3) OUTLETS ON NORTH AND EAST WALLS OF BREAKFAST ROOM ARE DEAD 4) VENT PIPING AND COMBUSTION SUPPLY AND RELIEF GRILLES ARE NOT INSTALLED FOR THE WATER HEATER AND ROOM FOR THE MASTER BATH (WEST END OUTSIDE)