Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/20/2002 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/17/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO POWER TO OUTLETS IN THE DINING ROOM 2) OUTLET ON SOUTH WALL SOUTH OF SLIDING GLASS DOOR IN LIVING ROOM IS DEAD 3) OUTLETS ON NORTH AND EAST WALLS OF BREAKFAST ROOM ARE DEAD 4) VENT PIPING AND COMBUSTION SUPPLY AND RELIEF GRILLES ARE NOT INSTALLED FOR THE WATER HEATER AND ROOM FOR THE MASTER BATH (WEST END OUTSIDE) |