Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/25/2002 FRAMING Approved IVRS - Inspection 0000*
03/22/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) DRAINAGE/VENT TEST NOT READY-EMPTY 2) HOLDOWN AT MASTER PATIO DOOR MOVED 1" NORTH WHEN KITCHEN ? 3) SEAL MESH PROTRUSION AT GAS MAIN AND ELECTRIC UNDER MAIN PANEL
03/20/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) ADD RED HEAD EAST SIDE OF GARAGE AND HOLD DOWN AT REAR GARAGE 2) SHIM TRIMMERS, HEADERS AND CRIPPLES WHERE NEEDED 3) ADD REDHEAD AT REAR RIGHT BEDROOM EAST WALL 4) CLIP ALL LEDGERS THAT ARE NOT CLIPPED 5) (PAGE 4) HEADER ABOVE ARCH, BETWEEN KITCHEN AND FRONT ENTRY, NEEDS 4 X 4 POSTS (B.U.) 6) STRAP ALL NON-CABIN TIED, INTERSECTING TOP PLATES 7) ATTACH 3RD FIREPLACE FLUE STRAP 8) TIGHTEN HOLDOWN AT MASTER PATIO DOOR 9) TIGHTEN HOLDOWNS IN LIVING ROOM 10) GAS TEST NOT READY 11) DRAINAGE TEST NOT READY 12) WATER SUPPLY OK-3/20