Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/02/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) ABS DWV THRU ROOF OK WATER TEST OK 2.) COPPER OK PRESSURE TEST OK 3.) OK TO COVER. |
| 05/01/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) 1" FLUSH VALVE REQUIRES ONE INCH COPPER SUPPLY NOT 3/4" MAY NOT INCREASE AT THE FLUSH VAVLE 2.) FLASH HANDLE FOR ADA TO BE ON THE WIDE SIDE OF THE OPENING 3.) NO WATER TEST ON ABS. 4.) NO ROOF JACK ON VENT. |