Permit: T02CM01073

Parcel: 12414115A


Addresses:

510 S HIGHLAND AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/02/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) ABS DWV THRU ROOF OK WATER TEST OK 2.) COPPER OK PRESSURE TEST OK 3.) OK TO COVER.
05/01/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) 1" FLUSH VALVE REQUIRES ONE INCH COPPER SUPPLY NOT 3/4" MAY NOT INCREASE AT THE FLUSH VAVLE 2.) FLASH HANDLE FOR ADA TO BE ON THE WIDE SIDE OF THE OPENING 3.) NO WATER TEST ON ABS. 4.) NO ROOF JACK ON VENT.