Permit: T02CM01052

Parcel: 112051620


Addresses:

2161 E GLENN ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM01052

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2002 FRAMING Approved IVRS - Inspection 0000*
03/15/2002 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) ELECTRIC SUB PANEL REQUIRES AN ISOLATED NEUTRAL BAR 2) DRYER DU CT REQUIRES RIGID DUCT IN WALL 3) GAS LINE NOT IN 4) ALL SWITCHES AND OUTLETS MUST BE GROUNDED 5) CONNECT ALL GROUNDS IN ELECTRIC BOXES TOGETHER AND SECURE WITH MECHANICAL FASTENERS AND GROUND ALL METAL ELECTRIC BOXES 6) SMOKE DETECTORS REQUIRED TO BE 36" FROM SUPPLY AIR 7) BATH0ROOM GFCI MUST BE ON A DECDICATED 20 AMP CIRCUIT ALSO KITCHEN COUNTER GFCI FRIG IS OK 8) SMOKE DETECTORS MUST BE INTER CONNECTED 9) DRYER MUST BE 4 PRONG OUTLET