Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2002 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 02/27/2002 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/ 1) FOUNDATION APPEARS TO BE TO SHALLOW ON 6" BELOW GRADE, PHOTOS INDICATE ONLY A #3 OR #4 REBAR IN FOOTING. EXPOSE FOOOTING AROUND ENTIRE SLAB. PROVIDE CITY OF TUCSON APPROVED DETAIL FOR PROVIDING PROPER FOOTING 2) GAS LINE CANNOT BE UNDER SLAB-CAP AND ABANDON AND REROUTE 3) UNDER SLAB D.W.V. PLUMBING IS NOT PER CODE. SANITARY "T" FITTINGS NOT ALLOWED IN THE HORIZONTAL POSITION-W/C HEAL VENTED. REPLACE ALL UNDER SLAB D.W.V. PLUMBING |