Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02CM01018

Parcel: 11706081D


Addresses:

400 N TOOLE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM01018

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL SUBJECT TO STATE MANFACTURED HOUSING INSPECTIONS.
03/26/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) GRATE COVER NEED TO BE SOLIDLY SUPPORTED TO ACCOMADATE THE WEIGHT OF A LARGE MAN. 2.) PLEASE SEAL ENTRANCE WHERE CONDUITS ENTER.
03/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) MAINTAIN WORKING CLEARENCE IN FRONT OF DISCONNECT #3 110-26. 2.) FINISH ITEMS #1 & #2. I NEED ACCESS TO BASEMENT TO SEE CONNECTION 3.) PLEASE EXPOSE GROUND RODS FOR INSPECTION TO VERIFY NOTE #4.
03/17/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) EMT FITTINGS NEED TO BE LISTED FOR USE IN DAMP AND WET LOCATIONS. 2.) PLEASE FINISH 4" PVC CONDUIT. 3.) PLEASE LABEL ALL DISCONNECTS AND PANELS. 4.) ISOLATION TO BE EQUAL FOR SPLICES IN JUNCTION BOX. 5.) A SPLIT BOLT IS LISTED FOR ONLY 2 WIRE.6.) CONDUCTOR TO BE TERMANATED CORRECTLY 7.) BREAKER DO NOT MEET THE REQUIREMENT FOR A/C RATING NOTE #11. 8.) PLEASE VERIFY JUNTION BOX SIZING PER CODE. 9.) TRAILER #3 DISCONNECT AS ON PLANS NOT INSTALLED PLEASE REVISE PLANS OR INSTALL AS DRAWN. 10.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED TERMAN 11.) PLEASE INSTALL GROUNDING ELECTRODE SYSTEM AS PER PLANS NOTE #4.