Inspection History: ELECTRIC - FINAL
Permit Number - T02CM01018
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL SUBJECT TO STATE MANFACTURED HOUSING INSPECTIONS. | |
03/26/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) GRATE COVER NEED TO BE SOLIDLY SUPPORTED TO ACCOMADATE THE WEIGHT OF A LARGE MAN. 2.) PLEASE SEAL ENTRANCE WHERE CONDUITS ENTER. | |
03/25/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) MAINTAIN WORKING CLEARENCE IN FRONT OF DISCONNECT #3 110-26. 2.) FINISH ITEMS #1 & #2. I NEED ACCESS TO BASEMENT TO SEE CONNECTION 3.) PLEASE EXPOSE GROUND RODS FOR INSPECTION TO VERIFY NOTE #4. | |
03/17/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) EMT FITTINGS NEED TO BE LISTED FOR USE IN DAMP AND WET LOCATIONS. 2.) PLEASE FINISH 4" PVC CONDUIT. 3.) PLEASE LABEL ALL DISCONNECTS AND PANELS. 4.) ISOLATION TO BE EQUAL FOR SPLICES IN JUNCTION BOX. 5.) A SPLIT BOLT IS LISTED FOR ONLY 2 WIRE.6.) CONDUCTOR TO BE TERMANATED CORRECTLY 7.) BREAKER DO NOT MEET THE REQUIREMENT FOR A/C RATING NOTE #11. 8.) PLEASE VERIFY JUNTION BOX SIZING PER CODE. 9.) TRAILER #3 DISCONNECT AS ON PLANS NOT INSTALLED PLEASE REVISE PLANS OR INSTALL AS DRAWN. 10.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED TERMAN 11.) PLEASE INSTALL GROUNDING ELECTRODE SYSTEM AS PER PLANS NOTE #4. |