Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 12/13/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*ENTRANCE PARTIAL APPROVED WILL NEED TEMP POWER CALL & LABELING. @ GUTTER AND DISCONNECT. | |
| 12/11/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1. NEED GROUND BUSH AND BOND JUMPER @ ALL NIPPLE FOR SERVICE EQUIPM. EG. @ C.T. RISER, GUTTER NIPPLE ETC. 2.) TERMINAL LUGS AT GUTTER DOES NOT ALLOW THE PROPER MIN BOND RODIUS FOR 350 MCM. 3.) NEED NEUTRAL AND NEUTRAL DISCONNECT AT END SERVICE DISCONNECT. |
|
| 11/27/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*WALLS APPROVED. | |
| 09/27/2002 | ELECTRIC - INTERMEDIATE | Partial Approval |