Permit: T02CM01009

Parcel: 14021011A


Addresses:

1105 E DREXEL RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/10/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
12/13/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*ENTRANCE PARTIAL APPROVED WILL NEED TEMP POWER CALL & LABELING. @ GUTTER AND DISCONNECT.
12/11/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1. NEED GROUND BUSH AND BOND JUMPER @ ALL NIPPLE FOR SERVICE EQUIPM. EG. @ C.T. RISER, GUTTER NIPPLE ETC.
2.) TERMINAL LUGS AT GUTTER DOES NOT ALLOW THE PROPER MIN BOND RODIUS FOR 350 MCM.
3.) NEED NEUTRAL AND NEUTRAL DISCONNECT AT END SERVICE DISCONNECT.
11/27/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*WALLS APPROVED.
09/27/2002 ELECTRIC - INTERMEDIATE Partial Approval