Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 11/13/2002 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*1.) PROVIDE RFI FOR ANCHORING SHEAR WALLS, THEY DO NOT HAVE THE 1/2" DIAMETER ANCHORS AS PER 105/54. 2.) WHERE ARE SPECIFICATIONS REFERED TO IN SUBNOT ON A1.0 ALLOWING METAL STUD SUBSTITUTION FOR INTERIOR FRAMING? |
|
| 11/06/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000*PARTIAL 1 EXIT WALLS & INTERIOR SHEAR WALLS. 2.) WEDGE ANCHORS REQUIRED ON INTERIOR SHEAR WALLS. |