Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 02/28/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 02/27/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*/ 1) INADEQUATE GROUND INSTALL 2 EACH 8 FOOT GROUND RODS AT LEAST 6 FEET APART CONNECTED TO SERVICE PANEL WITH A CONTINUOUS #4 COPPER CONDUCTOR 2) SUB PANEL MUST HAVE AN ISOLATED NEUTRAL-REMOVE JUMPER AND RELOCATE NEUTRAL TO NEUTRAL BAR |