Permit: T02CM00976

Parcel: 10820099A

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
02/28/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
02/27/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*/ 1) INADEQUATE GROUND INSTALL 2 EACH 8 FOOT GROUND RODS AT LEAST 6 FEET APART CONNECTED TO SERVICE PANEL WITH A CONTINUOUS #4 COPPER CONDUCTOR 2) SUB PANEL MUST HAVE AN ISOLATED NEUTRAL-REMOVE JUMPER AND RELOCATE NEUTRAL TO NEUTRAL BAR