Permit: T02CM00963

Parcel: 117100920


Addresses:

400 N TOOLE AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02CM00963

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/11/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/1)PLUMBING FINAL OK
2)OK FOR C OF O PENDING ANY OTHER INSPECTION
08/06/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) CAP OFF HOSE BIBS CORRECTLY REQUESTED ON 7/29/04 2) ON 4/16/04 INSPECTOR GAVE YOU THE HEADS UP ABOUT VERIFICATION OF GRADE-A LETTER FROM THE PLUMBING CONTRACTOR IS NOT ACCEPTABLE 3) ALL CLEANOUTS UTILIZING CHROME PLATED CLEANOUT COVERS REQUIRE COUNTER SUNK TAPPED PLUGS WITH MACHINE SCREW. RAISED SQUARE HEAD TEST PLUGS WITH A WOOD SCREW IS NOT ACCEPTABLE 4) REMOVABLE SERVICE PANEL ON EWC NEEDS TO BE REMOVABLE. UNABLE TO INSPECT PLUMBING BEHIND PANEL 5) INSPECTED BEHIND BOTH EWC-OK
08/02/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) SEE NOTES FROM 4/16/04 AND 7/29/04 2) CONTRACTOR TO PAY RE-INSPECTION FEE
07/29/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) CAP OFF 1/2" H20 IN SOUTH AREA AND 3/4 H20 SAME AREA CORRECTLY 2) HAVE FLOOR CLEANOUTS TO GRADE WITH CORRECT COVERS 3) PROVIDE 4" PERM CAP ON 4" LAST IRON PIPING IN UPSTAIRS AHU ROOM IN SOUTH END
07/22/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :ANCHOR EXPANSION TANKS
PROVIDE ACCESS TO WHA & TRAP PRIMERS
CAP OFF 1 1/2" FUTURE WATER STUB
REPAIR W/C 2ND FLOOR MENS
07/09/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) E.R.M. OFF SET PVC PIPING AROUND COLUMN FOR LIGHT POLE 2) CORRECTIONS MADE OK 3) OK TO COVER
04/21/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/16/2004 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PLBG IS COMPLETE. 2) CONTRACTOR NEEDS TO PROVIDE VERIFICATION OF GRADE ON SITE SEWER AND CERTIFICATION OF BACKFLOW DEVICES AND PLBG WILL BE COMPLETE.