Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 04/16/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE 30" OF WORKSPACE AT FURNACE PLATFORM 2) EXHAUST FAN AT MASTER BATH NOT HOOK UP TO EXHAUST HOSE 3) TIGHTEN NUT AT HOLDOWN IN GREAT ROOM 4) TIGHTEN HD'S AT GARAGE WALL 6) REMOVE COMBUSTIBLES 1" AWAY FROM WATER HEATER FLUE 7) FIRE BLOCK MISSING AT WATER HEATER PLENUM 8) FRONT DOOR EXTERIOR FIXTURE NOT GROUNDED 9) CLEAN OUT WEST WALL LEAKING |