Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02CM00944

Parcel: 11004345C


Addresses:

3315 N SWAN RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T02CM00944

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2002 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
CONDENSATE DRAINS ARE OK.
DUCT SMOKE DETECTORS ARE OK.
OK FOR CEILING TILES.
10/28/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*INSPECTION EXHAUST & SUPPLY IN RESTROOM. PARTIAL ON SUSPENDED ROUGH DUCT. OK TO PROCEED WITH GRID. PLANS SHOW 3" MIN. CLEARANCE INSIDE GREASE DUCT SHAFT. 2000 IMC REQUIRES 6" CLEARANCE.