Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T02CM00944
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2002 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* CONDENSATE DRAINS ARE OK. DUCT SMOKE DETECTORS ARE OK. OK FOR CEILING TILES. |
|
10/28/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*INSPECTION EXHAUST & SUPPLY IN RESTROOM. PARTIAL ON SUSPENDED ROUGH DUCT. OK TO PROCEED WITH GRID. PLANS SHOW 3" MIN. CLEARANCE INSIDE GREASE DUCT SHAFT. 2000 IMC REQUIRES 6" CLEARANCE. |