Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/09/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK C OF O. |
| 12/06/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NOTES: COMPLETE WIRING IN PANELS 2) INSTALL PANEL SCHEDULES 3) DISCONNECT SWITCHES IN VIOLATION OF WORKING CLEARANCE 2) ON ROOF ONE ON SODA DISPENSER NEED 36" CLEARANCE IN FRONT 110-26 NEC. |
| 11/22/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*SENT TO TEP ON 11/25/02 AT 9:15AM OK TO CLEAR TEMP POWER FOR TEST. |