Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2002 | ELECTRIC - ABOVE CEILING | Approved | ||
| 11/22/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
| 11/21/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
| 11/19/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) GO THOUGH AND CHECK SET SCREW COUPLINGS & CONNS. LOOSE. 2.) SUPPORT CONDUIT WITHIN 3' EACH TERMINATION 3.) BOND WATER & GS. 4.) CONNECT WALK IN COOLERS. |