Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/24/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO COVER |
| 05/22/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) SCH 40 USED ON RISER TO ELECTRIC METER SCH 80 REQUIRED 2) REVISE PLANS TO REFLECT AS BUILT 3) TIE GROUNDS TO METAL ELECTRIC BOXES AND MAKE UP ALL BOXES 4) NEED TO VERIFY SCH 40 IS 24" DEEP |