Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) BLDG. DRAIN IS STUBBED OUT @ TWO WAY C.O. ONLY. 3.) OK FOR BACKFILL. |
| 10/22/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) 2" BLDG. DRAIN REQUIRES A MIN OF 1/4" PER FT OF GRADE. 2.) RETEST SYSTEM WHEN 4" C.O. HAS BEEN INSTALLED. |