Permit: T02CM00877

Parcel: 11205047B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/26/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*WATER HEATER IN KIT AREA DISCONNECT ADDED 3 WATER HEATER UNDER SINKS REMOVED WIRING DISCONNECTED.
03/25/2003 ELECTRIC - FINAL Partial Approval PARTIAL ALL BUT #4. FINISHED.
03/19/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) APPROVED EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE.
2.) FIXTURE TO BE ATTACHED TO GRID.
3.) EXIT SIGNS NEED SUPPORT WIRES.
4.) WATER HEATERS TO HAVE DISCONNECTING MEANS
5.) MAINTAIN WORKING SPACE IN FRONT OF DISCONNECT 5.2.4
6.) OPEN PANEL S NEXT INSPECTION.