Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*WATER HEATER IN KIT AREA DISCONNECT ADDED 3 WATER HEATER UNDER SINKS REMOVED WIRING DISCONNECTED. | |
| 03/25/2003 | ELECTRIC - FINAL | Partial Approval | PARTIAL ALL BUT #4. FINISHED. | |
| 03/19/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) APPROVED EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE. 2.) FIXTURE TO BE ATTACHED TO GRID. 3.) EXIT SIGNS NEED SUPPORT WIRES. 4.) WATER HEATERS TO HAVE DISCONNECTING MEANS 5.) MAINTAIN WORKING SPACE IN FRONT OF DISCONNECT 5.2.4 6.) OPEN PANEL S NEXT INSPECTION. |