Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 04/26/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Approved |
IVRS - Inspection 0000*CORRECTION HAVE BEEN MADE OK TO BACKFILL. |
| 04/23/2002 |
PLUMBING - SEWER HCS CONNECT |
|
Denied |
IVRS - Inspection 0999*1.) A GRADE C.O. IS REQUIRED WHERE THE BLDG. DRAIN AND BLDG. SEWER CONNECT. 2.) NO BRIDGEING ALLOWED MUST SHADE ENTIRE 4" SEWER. 3.) 4" BLDG SEWER REQUIRES 12" OF COVER OR USE APPROVED MATERIAL. 4.) RETEST SYSTEM. |