Permit: T02CM00874

Parcel: 12517032A


Addresses:

3805 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
04/26/2002 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection 0000*CORRECTION HAVE BEEN MADE OK TO BACKFILL.
04/23/2002 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection 0999*1.) A GRADE C.O. IS REQUIRED WHERE THE BLDG. DRAIN AND BLDG. SEWER CONNECT. 2.) NO BRIDGEING ALLOWED MUST SHADE ENTIRE 4" SEWER. 3.) 4" BLDG SEWER REQUIRES 12" OF COVER OR USE APPROVED MATERIAL. 4.) RETEST SYSTEM.