Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02CM00863


Addresses:

7677 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM00863

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
04/21/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*FINISH #4 OF INSPECTION DATED 4/7/03 ALL OTHER ITEM TAKEN CARE OF.
04/08/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
04/07/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
04/04/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) FINISH INSTALLATION OF WIREWAY COVERS.
2.) FINISH INSTALLATION OF WIREWAY COVERS.
3.) FINISH ITEMS #2,3,4, OF PREIOUS INSPECTION.
4.) FINISH VERIFICATION OF LISTING LABELING.
OK TEMP C OF O SUBJECT TO INSPECTIONS MANAGER.
04/03/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) MISSING JUNCTION BOX COVERS AT REGISTRARS VDV.
2.) FINISH SUPPORTING CONDUITS AT REGISTRARS OUTSIDE STORE.
3.) MISSING JUNCTION BOXES COVERS.
4.) BONDING DEVICE AT CONCENTRIES OVER 250V.
3.) FUSE TO MATCH AMPACITY OF CONDUCTORS.
4.) FINISH SIGNS AS PER 700-8.
5.) IDENTIFY GROUNDED CONDUCTORS AT POLES.
04/02/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) WORKING CLEARENCE STILL AT RTU-1, RTU 3, & R TO 5.
OK AREAS AS MARKED.
04/01/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
03/31/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK PAINT MIXERS.
OK AREAS AS MARKED.
1.) PLEASE VERIFY LABELING FOR TINTING MACHINES, KEY MACHINES.
03/26/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) MAINTAIN WORK IN CLEARENCES IN FRONT OF DISCONNECT MEAN FOR A/C UNITS.
2.) TIGHTEN LOOSE FITTINGS.
3.) WE HAVE MULTIPOLE TERMANATIONS AT GOUND LUG STORE:
4.) CORD CAN NOT BE USED FOR PERMANENT WIRING METHODS 400-7 & 8.
OK 4 POLE BASES AND CONDUIT AS MARKER.
03/24/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TOOL RENTAL AREA. OK ISLES AS MARKED.
03/19/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK AS MARKED ON PLANS.
03/17/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*garden area:
1.) support conduit as per code at cash registrars
2.) tighten loose fittings.
03/14/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
03/13/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK HANGING LIGHTS APPLIANCE AREA, PRINT CENTER OK POWER PAINT CENTER.
2.) PLEASE VERIFY LABELING FOR PAINT MIXING MACHINE 110-3.
3.) A DUAL SUPPLY FOR FUEL AT GENERATOR IS NEEDED 700-12(B)(3).
03/11/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK AS MARKED.
03/07/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK POES REAR OF STORE NORTH SIDE.
03/05/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
03/04/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*FINISH SUPPORTING VDV CABLES AS PER CODES 700,800,300-11.
2.) MAINTAIN DEDICATED SPACE ABOVE PANELS.
3.) PLEASE LABEL DISCONNECTS
OK ROOM #113,112,111,109.
03/03/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) CORRECT GROUNDING AT WIRE MACHINE.
OK FOR ELECTRIC ON ROWS MARKED ON PLANS.
02/28/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TEMP C OF O FOR STOCKING OF NON-ELECTRICAL AREAS. AREAS WITH ELECTRICAL TO BE INSPECTED WILL BE RELEASED AS COMPLETED.
RECIEVED GENERATOR START UP PAPER WORK FOR FILES. A LETTER AND PAPERWORK TO BE SUBMITTED TO THE CITY ONCE YEARLY AS PER CODE 700-4(B).
02/27/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE TIGHEN PRE FAB ELECTRICAL ASSEMBLYS.
02/25/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
I WITNESSED GENERATOR TEST PLEASE PROVIDE TEST PAPER WORK.
1.) SPLIT BOLTS LISTED FOR RUN & TAP ONLY LIGHT POLES.
2.) A BONDING DEVICE IS NEEDED OVER 250 V AT CONCENTICS.
3.) PLEASE USE A CRIMP FOR GROUND AT BOX CRUSHER CONTROL PANEL.
4.) SIGNS FOR GENERATOR AS PER 700-8 ARE NEEDED.
02/24/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK 3/4" PVL AS MARKED.
OK POLE BASE GROUNDING EXCEPT BASE AT DOCK.
02/12/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
02/10/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*FILL UNUSED OPENING IN BOXES.
PARTIAL OFFICES & BATHROOMS EAST.