Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM00863
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
02/10/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
02/07/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
02/06/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK MAIN CONDUIT RUNS IN TRUSSES. | |
02/05/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
02/04/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
02/03/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
01/31/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 3 POLE BASES AND 3/4" CONDUIT AS MARKED. | |
01/30/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 1 POLE BASE & 3/4" PVC IN TRENCH AS MARKED ANSWERED QUESTION ON GENERATOR. | |
01/29/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
01/27/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK BONDING TO WATER AND STEEL 2) OK TEMP POWER FOR TEST | |
01/24/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*NEED LETTER FROM ENGINEER REGARDING SERVICE AS DISCUSSED. 2.) RECIEVED PAPER WORK FOR VALVES AND SAFTEY PRODURES FOR POWER USAGE. |
|
01/23/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK CONNECTIONS TO MDP A & B. OK CONNECTIONS OUT TO FLOOR PANELS. OK AS MARK 3/4" PVC. |
|
01/22/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) MAIN SWITCH GEAR HAS BREAKER AND PLANS CALL FOR FUSED DISCONNECT. 2.) TIGHTEN LOOSE CONNECTIONS 3.) PLEASE RAISE UNDERGROUND CONDUIT TO 2" ABOVE SLAB. |
|
01/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
01/03/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
01/02/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
12/31/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | ENTRANCE CANOPY SOFFIT AREA OK TO COVER OVERHEAD FIXTURES WEST SIDE. | |
12/18/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*PARTIAL POLE BASES ONLY SEE COOLEY JOB PLANS, GREEN HIGHLIGHTER MARKED APPROVED. | |
12/16/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*ok data and cash room. | |
12/02/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* |