Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM00766

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/03/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
08/29/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) MULTI GANG BOXES HAVE ROME TABS PULLED OUT. ROMEX MUST BE SECURED TO THE BOX ONLY EXCEPTION IS SINGLE GANG PLASTIC. 2.) ROMEX NOT BE BUNDLED TOGETHER MORE THAN 2' IN LENGTH WITHOUT DERATING. 3.) ROMEX NOT ALLOWED UNDERGROUND, MUST BE UF.