Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/10/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) HCS CONNECTION IS OK 3.) OK TO BACKFILL TRENCH. |
| 10/09/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999* 1) DO NOT CALL UNTIL 100% COMPLETE |