Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM00712
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
05/23/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) FLOOR CUTS NEED ENGINEERS APPROVAL 2) CONTINUE WITH ALL ELSE | |
05/22/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) ENGINEERS APPROVALS, FOR MASTER BATH CUT AND REPAIR AND FOR CUT IN KITCHEN FLOOR, HAVE NOT BEEN PROVIDED 2) GAS PIPING ABOVE MASTER BATH NEEDS SUPPPORTS AND CLAMPS | |