Permit: T02CM00705

Parcel: 116211160

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
05/06/2002 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection 0000*HANDOUT GIVEN TO BUILDER PARTIAL FOR NO. 2 PLEASE DO NO STOCK GROUNDING LUGS IN GUTTER USE MULTIPLE ATTACHED TO LUG GUTTER. WILL CHECK ON.
05/01/2002 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection 0210*A BONDING JUMPER IS REQUIRED AT (2) BUSHINGS PLEASE HAVE APPROVED PLANS DEPICTING SERVICE ACCURATELY IE. GUTTER WIRE SIZE ETC. A SPLIT BOLT CONNECTOR IS APPROVED FOR 2 CONDUCTOR ONLY EG. A RUN AND TAP ONLY. LOOSE CONNECTIONS AT SPLIT BOLT WRONG SIZE OF SPLIT BOLT. CENTER CU & AL. SEPARATOR REMOVED INSUFFICIENT INSULATION. PERMANENTLY ADDRESS SERVICE REMOVE T.V. & TELE. CABLES FROM DEDICATED SPACE BELOW PANEL BOARD.