Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2002 |
ELECTRIC - UFER |
|
Approved |
|
| 04/30/2002 |
ELECTRIC - UFER |
|
Not ready for Inspection |
NOT APPROVED POURED W/OUT INSPECTION WILL NEED TO PROVIDE IN APPROVED PLAN AN ALTERNATE METHOD OF GROUND ELECTRODE SYSTEM. |
| 02/28/2002 |
ELECTRIC - UFER |
|
Denied |
IVRS - Inspection 0225*1.) SERVICE DIAGRAM PLANS DO NOT REFLECT THIS TYPE OF INSTALLATION PLEASE REVISE PLANS OR INSTALL AS PER PLANS. 2.) IF USE THIS INSTALLATION PLEASE RELOCATED ONE OF THE CLAMPS TO THE SAME REBAR ROW TO UTILIZE BONDING OF SERVICE PER ART 250-58. |