Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/21/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*THE BOOTH WIRING IS ACCEPTABLE TO MANAGEMENT AND MAINTENANCE |
| 09/19/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) REMOVE LINE & LOAD WIRING FROM MAGNETIC ROUTE LINE TO DISCONNECT. 2.) WIRING OF CONTROL AND EQUIPMENT USED ARE NOT PER PLAN 3.) CIRCUIT ASSIGNMENT FROM PANEL DIFFERS FROM PLAN. 4.) WIRING IS NOW SINGLE PHASE US PLAN 3 PHASE. 5.) SHOP FAN WIRING 480 VOLT COLORS USED ON 120/208 VOLT EQUIPMENT. 6.) CONDUIT NIPPLE THRU WALL IS SHORT AT DISCONNECT NEED CONDUIT PROPERLY TERMINATED WITH LOCKNUT. 7.) IDENTIFY ALL CIRCUITS AT DISCONNECTS. 8.) IDENTIFY ALL MAGNETICS WITH EQUIPMENT SERVED. IDENTIFY CIRCUITS AT PANEL. ENGINEER OF RECORD IS ONLY PERSON AUTHORIZED TO REVISE PLANS. |