Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM00694
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
02/14/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) PLEASE PROVIDE FIRE PROTECTION AND/OR SEPERATION IN FIRE WALLS. PER CODE 300-21. 2.) WE HAVE OPEN SPLICES AND EXPOSED CONDUCTORS IN THE WALL BETWEEN KITCHEN. 3.) PLEASE SUPPORT NM CABLE ABOVE THE SUBPANEL 4.) NM CABLE IS TO BE SUPPORTED WITHIN 12" OF BOXES AND EXHAUST FANS. |