Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/30/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
12/26/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0935*UNITS INCORRCTLY FUSED. MAX FUSE SIZE, ELECT. DATA PLATE,. 35 AMPS. UNIT CIR BKR. 40 AMPS AT PANEL NON FUSED SWITCH AT UNIT.
12/24/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0935*
12/20/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
12/11/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*SEE NOTES LOT #1.