Permit: T02CM00690

Parcel: 133233340


Addresses:

1054 N PRESSYC PL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/18/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
06/18/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*SEE NOTICE LOT 1 SHEET.
06/14/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*UNBUNDLE HOME RUN CABLES. SUPPORT IN SMALL GROUPS DO NOT USE ROMEX OR ROMEX JACKET FOR SUPPORT OF CABLES THESE ARE NOT APPROVED FOR THE PURPOSE.
06/12/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*NOTES 1.) CABLE BUNDLED IN LENGHTS EXCEEDING 24" TO BE DERATED PER ART. 310-15 NEC.