Permit: T02CM00637

Parcel: 12620001A


Addresses:

3455 E ZOO CT


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02CM00637

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/CORRECTION MADE
11/05/2004 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
11/01/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) BOILER TO HAVE GAS VALVE PRIOR TO UNION OR USE LEFT-RIGHT NIPPLE COUPLING 2) PROVIDE CORRECT COUPLING AT WATER HEATER VENT. (SHIELD COUPLING) 3) PROVIDE HANGER FOR WATER HEATER UPPER HORIZONTAL VENT 4) INSTALL SHOCK STOP IN MENS REST ROOM URINAL WALL 5) INSTALL SHOCK STOP IN WOMENS RESTROOM CLOSET WALL 6) PROVIDE CORRECT BTU RATED ASME RELIEF VALVE ON POOL HEATER AND ALL PIPING TO GRAVITY DRAIN TO FLOOR PIT AREA (THERAPY POOL) 7) ALL WATER IN POOL EQUIP BLDG IS NON-POTABLE AND HOSE BIBS, AND EYE WASHER SHOWER TO HAVE SINGS STATING SO 8) PROVIDE ALL BACKFLOW CERTIFICATIONS, PROVIDE VERIFICATION OF GRADE ON SITE SEWER, PROVIDE BACTERIA REPORT FOR BLDG H20 SYSTEM. PROVIDE PROOF OF BOILER INSPECTION. CALL IN ALL POOL INSPECTIONS OK FOR TEMP C OF O
10/15/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) WASTE VENT AND H20 WATER TEST FOR (2) P-5B AND (2) P-7C OK