Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02CM00637
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/CORRECTION MADE | |
11/05/2004 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* | |
11/01/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) BOILER TO HAVE GAS VALVE PRIOR TO UNION OR USE LEFT-RIGHT NIPPLE COUPLING 2) PROVIDE CORRECT COUPLING AT WATER HEATER VENT. (SHIELD COUPLING) 3) PROVIDE HANGER FOR WATER HEATER UPPER HORIZONTAL VENT 4) INSTALL SHOCK STOP IN MENS REST ROOM URINAL WALL 5) INSTALL SHOCK STOP IN WOMENS RESTROOM CLOSET WALL 6) PROVIDE CORRECT BTU RATED ASME RELIEF VALVE ON POOL HEATER AND ALL PIPING TO GRAVITY DRAIN TO FLOOR PIT AREA (THERAPY POOL) 7) ALL WATER IN POOL EQUIP BLDG IS NON-POTABLE AND HOSE BIBS, AND EYE WASHER SHOWER TO HAVE SINGS STATING SO 8) PROVIDE ALL BACKFLOW CERTIFICATIONS, PROVIDE VERIFICATION OF GRADE ON SITE SEWER, PROVIDE BACTERIA REPORT FOR BLDG H20 SYSTEM. PROVIDE PROOF OF BOILER INSPECTION. CALL IN ALL POOL INSPECTIONS OK FOR TEMP C OF O | |
10/15/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) WASTE VENT AND H20 WATER TEST FOR (2) P-5B AND (2) P-7C OK |