Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T02CM00637
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* TOILET 109 WATER TEST WASTE & VENT THRU ROOF OK. STORAGE 118 3"RAIN DRAIN & OVERFLOW RAIN DRAIN WATER TEST OK | |
09/09/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
09/08/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/1)H20 PIPING IN MACH ROOM OK 2)100 PSI TEST ON HEATING WATER & CHILLED WATER PIPING OK |
|
08/13/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :WATER LINE FOR DECK MOUNT HYDRANT AT THERAPY POOL OK TO COVER | |
08/05/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/02/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) WATER TEST THERAPY POOL AREA DRAIN INTO RETENSION POND PER APPROVED PLAN OK | |
07/28/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) CUSTOMER CANCELLED | |
07/27/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection :DENIED. (1) PROVIDE CITY APPROVED PLAN WITH END OF LINE UPPER TERMINAL CLEANOUTS. (2) USE OF FITTINGS TO MAKE CHANGES OF DIRECTION SHALL BE USED. | |
06/08/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ H20 IN WALL AND OVERHEAD AND WASTE AND VENT OK. LOCKER ROOMS 121 AND 124 LAV. WALLS. | |
05/27/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ CORRIDOR 118, ROOM 131-135, LOCKERROOM 121, 124, TOILET 117, ABOVE CEILING AND INTERMEDIATE OK. | |
05/26/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/10/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ WTR TEST ROOF DRAINS - THERAPY POOL AREA, NORTH AND SOUTH DRY CORRIDOR 126 AND 125 PARTIAL APPROVAL PENDING CORRECT SPACING ON ALL PIPE HANGERS. | |
04/21/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ WTR TEST WASTE AND VENT FROM WET CORRIDOR 125 SOUTH OK EXCEPT VENT IN 122 AND 123 AND P7A AT SOUTH EXTERIOR. H20 AIR TEST 100 PSI OVERHEAD AND IN WALL OK EXCEPT SHOWERS FROM WEST END WET CORRIDOR 125 SOUTH AND SOUTHWEST HOSE BIB. | |
04/07/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1ΒΌ H2O FROM SOUTHWEST CORNER OF LOBBY TO STUB UP AT POOL SOUTH CENTER FOR WHEEL CHAIR LIFT. WILL NEED TO SEE HYDRANT CONNECTION AND BLD CONNECTION. | |
02/06/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ RESTROOM 121 AND 124 STOOL AND URINALS WALLS H20 IN BLOCK WALL PROPERLY ISOLATED FROM MASONARY. |