Permit: T02CM00637

Parcel: 12620001A


Addresses:

3455 E ZOO CT


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T02CM00637

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/13/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :* TOILET 109 WATER TEST WASTE & VENT THRU ROOF OK. STORAGE 118 3"RAIN DRAIN & OVERFLOW RAIN DRAIN WATER TEST OK
09/09/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/08/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/1)H20 PIPING IN MACH ROOM OK
2)100 PSI TEST ON HEATING WATER & CHILLED WATER PIPING OK
08/13/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :WATER LINE FOR DECK MOUNT HYDRANT AT THERAPY POOL OK TO COVER
08/05/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/02/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) WATER TEST THERAPY POOL AREA DRAIN INTO RETENSION POND PER APPROVED PLAN OK
07/28/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) CUSTOMER CANCELLED
07/27/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :DENIED. (1) PROVIDE CITY APPROVED PLAN WITH END OF LINE UPPER TERMINAL CLEANOUTS. (2) USE OF FITTINGS TO MAKE CHANGES OF DIRECTION SHALL BE USED.
06/08/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/ H20 IN WALL AND OVERHEAD AND WASTE AND VENT OK. LOCKER ROOMS 121 AND 124 LAV. WALLS.
05/27/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/ CORRIDOR 118, ROOM 131-135, LOCKERROOM 121, 124, TOILET 117, ABOVE CEILING AND INTERMEDIATE OK.
05/26/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/10/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ WTR TEST ROOF DRAINS - THERAPY POOL AREA, NORTH AND SOUTH DRY CORRIDOR 126 AND 125 PARTIAL APPROVAL PENDING CORRECT SPACING ON ALL PIPE HANGERS.
04/21/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ WTR TEST WASTE AND VENT FROM WET CORRIDOR 125 SOUTH OK EXCEPT VENT IN 122 AND 123 AND P7A AT SOUTH EXTERIOR. H20 AIR TEST 100 PSI OVERHEAD AND IN WALL OK EXCEPT SHOWERS FROM WEST END WET CORRIDOR 125 SOUTH AND SOUTHWEST HOSE BIB.
04/07/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1ΒΌ H2O FROM SOUTHWEST CORNER OF LOBBY TO STUB UP AT POOL SOUTH CENTER FOR WHEEL CHAIR LIFT. WILL NEED TO SEE HYDRANT CONNECTION AND BLD CONNECTION.
02/06/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ RESTROOM 121 AND 124 STOOL AND URINALS WALLS H20 IN BLOCK WALL PROPERLY ISOLATED FROM MASONARY.