Permit: T02CM00637

Parcel: 12620001A


Addresses:

3455 E ZOO CT

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/01/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK C OF O
11/30/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) LABELS ON MCC CONTROLLERS AND SWITCHES AT SERVICE MUST BE SCREWED OR RIVITED TO COVER
11/23/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PLEASE HAVE ELECTRICAL SUPERINTENDENT ON SITE OR SOMEONE WHO CAN DISCUSS JOB ( OUR HOURS ARE 7AM 3:30 PM. PLEASE RESCHEDULE AT 740-6970
10/29/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/1)2-PUMPS IN POOL EQUIP ROOM NOT CONNECTED YET. OK TEMP C/O TO INSTALL FRUNACE & SET UP OFFICES
10/15/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/8035-PARTIAL 2010 U.G. ELECT - APPROVED NOTES: 1)COMPLETE WIRING IN POOL EQUIP ROOMS, OPEN J-BOXES 2) DICONNECTS & MOTOR STARTERS MUST HAVE 36" WORKING CLEARANCE IN FRONT 3)LABEL DISCONNECTS IN POOL EQUIP ROOM 4)LABEL DISCONNECT SWITCHES IN MECH. YARD 5)PUMPS MOTORS IN MECH ROOM REQUIRE DISCONNECTS PER NEC-NOT IN SITE
07/06/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) CONTR. HAD QUESTION ONLY