Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM00637
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/11/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ OK TO CLEAR TEMP POWER FOR TEST - SUBJECT TO BOND POSTING TO TEST POOL EQUIP. NOTE THAT ELECTRICAL EQUIP TO BE LOCKED OUT WITH ONLY AUTHORIZED PERSONNEL TO HAVE ACCESS JOB SUPT. | |
05/03/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/28/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) NOTES PROVIDE LETTER OF TORQUE FOR SWITCH GEAR 2) RE-SIZE BOND BUSHING EQUIPMENT GROUND AT SECONDARY FEEDERS |
|
02/25/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
02/06/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ PUMP HOUSE BLDG. / BOX AND CONDUIT STUB-OUTS FOR LOCKER AND BATH AREA WALLS | |
01/09/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK ROUGH IN WALLS MASONRY FOR LOCKER ROOM, THERAPY ROOM, MECH AREA, UNDERSLAB BRANCH CIRCUITS FOR LOBBY. |