Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/21/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
1.) SOIL WATER TEST IS OK 2.) HCS CONNECTION IS OK 3.) OK TO BACKFILL TRENCH. |
| 05/20/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) TRAP ARM FOR P-4 DOES NOT MEET THE MIN. TRAP ARM DISTANCE FROM CROWN OF P-TRAP TO BARREL OF WASTE LINE SEE SECTION 1002.2 94 UPC. 2.) BACK TO BACK WATER CLOSET TRAP ARMS CAN NOT INCREASE FROM 3" TO 4" A DBL. SAN CROSS 4 X 3 CAN BE USED IN STEAD OF 4 X 3 WYE. 3.) RE TEST SYSTEM. 4.) OK TO BACK TRENCH UP TO THESE AREAS. |