Permit: T02CM00635

Parcel: 141170140


Addresses:

8235 S HOUGHTON RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/21/2002 PLUMBING - ROUGH, SOIL Approved 1.) SOIL WATER TEST IS OK 2.) HCS CONNECTION IS OK 3.) OK TO BACKFILL TRENCH.
05/20/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) TRAP ARM FOR P-4 DOES NOT MEET THE MIN. TRAP ARM DISTANCE FROM CROWN OF P-TRAP TO BARREL OF WASTE LINE SEE SECTION 1002.2 94 UPC. 2.) BACK TO BACK WATER CLOSET TRAP ARMS CAN NOT INCREASE FROM 3" TO 4" A DBL. SAN CROSS 4 X 3 CAN BE USED IN STEAD OF 4 X 3 WYE. 3.) RE TEST SYSTEM. 4.) OK TO BACK TRENCH UP TO THESE AREAS.