Permit: T02CM00634

Parcel: 107040180

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/28/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*COMPLETE.
05/23/2002 ELECTRIC - FINAL Partial Approval TWO EBO FIXTURES MISSING IN WAREHOUSE BEING INSTALLED AT THIS TIME.
05/22/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*SUBJECT TO BUILDING INSPECTOR.
05/20/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PLEASE BOND GROUND BAR OR IDENTIFY AS ISOLATED GROUNDS 2.) PANEL NEED TO BE FLUSHED OUT TO PROTECT FROM COMBUSTABLES 3.) PLEASE TIGHTEN FITTINGS AT WATER HEATER. 4.) LABEL PANEL COVERS ON OUTSIDE. 5.) DISCONNECTS NEED TO BE LABEL AS TO WHICH PANEL THE SERVE. PLEASE CALL ALL INSPECTIONS RELATED TO TEMP POWER FOR TEST.
05/15/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) BONDING DEVICES ARE NEEDED AT SERVICE 250-94. 2.) PLEASE CLEAN UNDER LUGS 250-12. 3.) USE OF THE CORRECT SIZED LUG IN NEEDED 110-3,110-12. 4.) PLEASE TIGHTEN LUGS TO DISCONNECT. 5.) REJECTION PINS WILL BE NEEDED 6.) FINISH SUB PANELS 7.) POWER TO GATE OPENER NEEDS TO BE IN APPROVED RACEWAY. UNDERGROUND COVERED WITH OUT INSPECTION. 8.) PLEASE INSTALL DEVICES OR BLANK OFF FOR ALL OPENINGS BELOW 8' FOR TEMP POWER FOR TEST.