Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/28/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*COMPLETE. |
| 05/23/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
TWO EBO FIXTURES MISSING IN WAREHOUSE BEING INSTALLED AT THIS TIME. |
| 05/22/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*SUBJECT TO BUILDING INSPECTOR. |
| 05/20/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE BOND GROUND BAR OR IDENTIFY AS ISOLATED GROUNDS 2.) PANEL NEED TO BE FLUSHED OUT TO PROTECT FROM COMBUSTABLES 3.) PLEASE TIGHTEN FITTINGS AT WATER HEATER. 4.) LABEL PANEL COVERS ON OUTSIDE. 5.) DISCONNECTS NEED TO BE LABEL AS TO WHICH PANEL THE SERVE. PLEASE CALL ALL INSPECTIONS RELATED TO TEMP POWER FOR TEST. |
| 05/15/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) BONDING DEVICES ARE NEEDED AT SERVICE 250-94. 2.) PLEASE CLEAN UNDER LUGS 250-12. 3.) USE OF THE CORRECT SIZED LUG IN NEEDED 110-3,110-12. 4.) PLEASE TIGHTEN LUGS TO DISCONNECT. 5.) REJECTION PINS WILL BE NEEDED 6.) FINISH SUB PANELS 7.) POWER TO GATE OPENER NEEDS TO BE IN APPROVED RACEWAY. UNDERGROUND COVERED WITH OUT INSPECTION. 8.) PLEASE INSTALL DEVICES OR BLANK OFF FOR ALL OPENINGS BELOW 8' FOR TEMP POWER FOR TEST. |