Permit: T02CM00634

Parcel: 107040180

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/14/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
05/13/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999* 1.) IF SUPPORT FIXTURE WHIPS THEY NEED TO BE AS PER CODE 300-11 2.) WHEN USING MANFACTURES SUPPLIED HOLD DOWN CLIPS THEY NEED TO BE EFFICTIVE. 3.) CONDUIT BOXES TO BE SUPPORTED AS PER CODE 300-11 ALSO CONDUIT CAN NOT LAY UPON GRID. 4.) PLEASE TIGHTEN SET SCREWS FITTINGS AND LOCK NUTS. 5.) PLEASE HAVE OUTSIDE AGENCY STAMP PLAN REVISIONS.