Permit: T02CM00633

Parcel: 116193730

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/17/2003 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*1.) 60# AIR TEST OK
2.) AGA VALVES INSTALLED.
3.) MECHANICAL INSPECTOR INFORMED ABOUT GAS RELEASE.
4.) OK FOR GAS.
5.) UCC LEFT AT METER.
01/16/2003 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*NO PRESSURE TEST 60# MINIMUM WELD PIPE.
2.) ALL VALVES TO BE AGA OR CSA APPROVED
3.) PIPING FOR FUTURE BOILERS VALVES AND CAPPED OVERHEAD.
4.) PIPING INCOMPLETE TO WATER HEATER.