Permit: T02CM00633

Parcel: 116193730

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/27/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
02/25/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK ALL POLE LIGHTING SUBJECT TO LETTER
OK AIR TERMANALS AND GROUNDING ON ROOF.
1.) SUPPORT BOX & CONDUIT BOILER STB-1 (CONTROLS)
2.) PLEASE VERIFY IF VFD CAN BE USED INSIDE ENVIERMENTAL AIR OF AIR HANDLER 300-22.
3.) TIGHTEN LOOSE SEAL TIGHT FITTINGS INSIDE AIR HANDLER. 300-22.
4.) PLEASE PROVIDE A LETTER VERIFYING POLE HEAD MAKE UP AS PER MANUFACTURE INSTRUCTION.
02/07/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) SOME EMERGENCY LITES NOT WORKING. ARCHIVES & ATTU RM.
2.) BOILER ROOM EQPMT. BEING WIRED.
3.) LABEL AHU DISCONNECT ON ROOF.
02/06/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) EMERGENCY LIGHTING NEEDS ATTENTION 2) DISCONNECTS FOR ALL EQUIPMENT MUST BE MARKED WITH PANEL AND CIRCUITS SERVING THAT EQUIPMENT 3) TEMP C OF O APPROVED
01/03/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) MAINTAIN CLEARENCES AT VAV DISCONNECTING MEANS 502
2.) FINISH CONDUIT FOR FIRE ALARM.
OK ABOVE CEILING EXCEPT AS NOTED 310-313,406,502.
12/31/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) MAINTAIN WORKING CLEARENCES FOR VAV DISCONNECTING MEANS
2.) CLAMTIC TO FINISH FIRESTOPPING AND PROVED ASSEMBLY LISTING VERIFICATION
3.) FINISH VDV CABELING SUPPROT AS PER 300-11.
OK CONDUIT ABOVE CEILING ALL HALLWAY.