Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 08/08/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000*RECIEVED LETTER FOR TORQUE VALVES OBSERVED GFI TEST OF MAIN BREAKER AND RECEIVED TEST RESULTS.1.) FINISH GROUNDING ELECTRODES SYSTEM CONNECTIONS FOR GROUND RING. 2.) FINISH PAPERWORK FOR BOND AND TEMP POWER. |
| 08/02/2002 |
ELECTRIC - CABLE DROP |
|
Partial Approval |
1. BUILDING JUMPERS TO BE SIZED PER 250-102. 2.) PLEASE PROVIDE A LETTER VERIFYING TORQUE VALVES FOR ENTRANCE EQUIPMENT 3.) PLEASE PROVIDE GFI TEST AS PER 230-95. |