Permit: T02CM00633

Parcel: 116193730

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/06/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
02/04/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
01/29/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) ROOMS 601 AND 602 ABOVE CEILING 2) ROOM 604 AND 606-SHELL SPACE-ABOVE CEILING
01/22/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) RM 311 402,404,410, AND HALLS 401 & 09. FOR ABOVE CIELING.
01/13/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK ABOVE AS MARKED. EXCEPT FIRE STOPPING OF CABLE TRAY FOR A LATER DATE.
12/31/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
12/20/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK CANS IN SOFFETT RM #305, 308,HALL 501, 401
1.) HOLD CEILING FOR FIRE STOPPING HALL 401 AT FIRE DOOR.
12/18/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK CEILING AS NOTED RM #201-217
OK CANS IN SOFFET #501,407,401
OK FIRE STOPPING OF CONDUITS ROOM
OK WALL ROOM 403 WEST WALL
1.) SUPPORT WIRES NEEDED ON ALL BOXES IN GRID.
2.) FINISH SUPPORTING FLEX CONDUITS AT SMOKE DECTECTORS AND BOXES
3.) VERIFY FIRE STOPPING METHOD FOR CLIMATE
4.) PLEASE LEAVE OPEN AT CABLE TRAYS FOR FURTHER INSPECTION.
12/17/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK CANS IN SOFFETS HALL 102, 304. OK PANELS EPLA, ELHA, EPLA, EPLB, EPLC, DPA, SPLA, SWITCHBOARD MDS FOR FEEDS TO ABOVE PANELS MANUAL TRANSFER SWITCH TRANFORMER TR-1.
1.) CHECK ON PARRALELL CONDUCTOR LENGHTS 310-4 PNL "DPA"
2.) CABLE THROUGH FIRE WALL TO BE INSTALLED AS PER FIRESTOPPING SYSTEM REQUIREMENTS.
12/13/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK HARD CEILING FRONT ENTRY, CANS FOR #301,414. OK FIRE STOPPING 414.
OK PVC ACCROSS DRIVE FOR GATE MOVE UP 2" FOR CONCRETE ENCASEMENT.
1.) CHECK FOR FIRE PENTRATION OF RED CABLE PASSING THRU FIRE DOOR OUTSIDE #505.
12/11/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS & HARD CEILING 105,406,417 AS MARKED ON PLANS.
12/10/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK ROOMS 603,605,411,105. 1.) STOPPING OR PENITRATIONS IN ROOM 104,417.
12/05/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK SOFFIT RM #100 AND CEILING ROOM #302,303.
1.) PLEASE REQUEST INFORMATION FOR SERVICE ABILITY FOR LIGHTS IN BATHROOM SOFFITS.
11/27/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO ENERGIZE PANEL "WLHA" OK WALLS ROOM 102-114,501
11/20/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK CONDUIT ABOVE CEIL ROOM 201-217,416.
11/14/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK ROOMS 309-313, 401-405,508-510 AS MARKED.
11/12/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS 405-415 AS MARKED ON PLANS.
11/01/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS ROOM 503,507 EXTERIOR WALL 405,510,508 AND HALLWAY 409.
10/28/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) LIBRARY ROUGH IN CK #502 RM. 2.) CONFERENCE RM #101, ROUGH IN OK.
10/23/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*PARTIAL WALLS COLUMN C & D NORHT COLUMN 2 INCLUDED 2 SIDE BATHROOM 302/303 HALL 301. NOTE: THERMOSTATE @ HALL 301 LOOSE CONDUIT, CONNECTOR PLEASE TIGHTEN.
10/18/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS ROOM #201-205,209-212
10/15/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK CLIMATE SOUTH WALL OBJECTS REPOSTIORY.
10/11/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
10/10/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS ROOM 308 & 416
10/07/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK "T" STATS ARCHIEVE REPOSITORY AND OFFICES.
10/03/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK REPOSITORY FOR "T" STATS.
10/02/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) PLEASE UNCOVER WORK FOR INSPECTION. 2.) CONDUIT TO BE SUPPORTED WITHIN 3' OF BOXES AND FITTINGS AS PER CODE 348. 3.) TIGHTEN LOOSE FITTINGS.
09/27/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
09/20/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
09/16/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK AS MARKED.
09/13/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK AS MARKED.
09/11/2002 ELECTRIC - INTERMEDIATE Partial Approval OK EXTERIOR WALLS IN MECHANICAL AND ELECTRIC ROOMS OK TO ENERGIZE FOR "SLHA" TEMP POWER.
06/10/2002 ELECTRIC - INTERMEDIATE Partial Approval OK 4/0 IN TRENCH AS MARKED.