Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM00629
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
08/22/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) BEAM CLAMP NOT LISTED FOR GROUNDING. 2.) PLEASE PROVIDE A LETTER FROM ENGINEER REGARDING EXOTHERMIC WELDS. 3.) TIGHTEN FLEX CONNECTORS AT UPS BACK 4.) CAN NOT STACK LUGS IN DISCONNECT. 5.) LABEL DISCONNECT. 6.) BOND NEUTRAL TO GROUND AT TRANSFORMER. 7.) PLEASE PROVIDE A LETTER FOR FUSE TYPE NOT LISTED IS SPECIFICATIONS. |