Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/23/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/22/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) BEAM CLAMP NOT LISTED FOR GROUNDING. 2.) PLEASE PROVIDE A LETTER FROM ENGINEER REGARDING EXOTHERMIC WELDS. 3.) TIGHTEN FLEX CONNECTORS AT UPS BACK 4.) CAN NOT STACK LUGS IN DISCONNECT. 5.) LABEL DISCONNECT. 6.) BOND NEUTRAL TO GROUND AT TRANSFORMER. 7.) PLEASE PROVIDE A LETTER FOR FUSE TYPE NOT LISTED IS SPECIFICATIONS. |