Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM00580
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/07/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
03/03/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0935$DATA PLATA STILL NOT COMPLETED! DOES UNIT HAVE AUXILARY HEAT STRIP, YES?NO? NO HEAT ST. UNIT FUSES AT 30 AMPS. UNIT IS NOW FUSED AT 50 AMPS??? HAVE MECHANCIAL COUNT. CALL ME IF HE DOESNT UNDERSTAND. |
|
02/28/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*NOT HOME FOR INSPECTION. PLEASE CALL AGAIN WHEN SOMEONE WILL BE HOME. |
|
02/26/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*1.) Mark unit data plate w/proper heat kit installed & fuse unit accordingly. 2.) Have plans revised showing deletion of evap cooler & relief lowver. Recall for inspection. |