Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2002 |
BUILDING ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 04/10/2002 |
BUILDING ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) I NEED INSTALLATION STANDARD BEING USED FOR CEILING GRID. 2.) BOTH STANDARDS I AM AWARE OF CALL FOR 3 TURN OF SUSPENSION WIRE WITHIN 3". |
| 04/05/2002 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*PLEASE PROVIDE CEILING GRID INSTALLATION STANDARD THAT IS BEING USED. GENERAL NOTES FOR RCP ARE CALLING FOR POP RIVETS ON 2 ADJACENT SIDES SO I AM ASSUMING THA TTHE UBC INSTALLATION STANDARD IS BEING USED. IF SO, THEN PERIMETER WIRES ARE NEEDED WITHIN 8" OF WALL ON ALL MAIN & CROSSS RUNNERS. |
| 03/19/2002 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*HARD LIDS & INSULATION OK I STILL NEED TO SEE GRID. |