Permit: T02CM00573

Parcel: 13803031M


Addresses:

910 W VALENCIA RD

Inspection Status: Approved

Inspection History: BUILDING ABOVE CEILING

Date Description Inspector Results Comments
04/17/2002 BUILDING ABOVE CEILING Approved IVRS - Inspection 0000*
04/10/2002 BUILDING ABOVE CEILING Denied IVRS - Inspection 0999*1.) I NEED INSTALLATION STANDARD BEING USED FOR CEILING GRID. 2.) BOTH STANDARDS I AM AWARE OF CALL FOR 3 TURN OF SUSPENSION WIRE WITHIN 3".
04/05/2002 BUILDING ABOVE CEILING Partial Approval IVRS - Inspection 0000*PLEASE PROVIDE CEILING GRID INSTALLATION STANDARD THAT IS BEING USED. GENERAL NOTES FOR RCP ARE CALLING FOR POP RIVETS ON 2 ADJACENT SIDES SO I AM ASSUMING THA TTHE UBC INSTALLATION STANDARD IS BEING USED. IF SO, THEN PERIMETER WIRES ARE NEEDED WITHIN 8" OF WALL ON ALL MAIN & CROSSS RUNNERS.
03/19/2002 BUILDING ABOVE CEILING Partial Approval IVRS - Inspection 0000*HARD LIDS & INSULATION OK I STILL NEED TO SEE GRID.