Permit: T02CM00534

Parcel: 107051080


Addresses:

2928 N 15TH AV #12


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T02CM00534

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
04/24/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) WE HAVE ZIP CORD RUN INTO THE CEILING FOR A PERMNENT WIRING METHOD. 2.) COOLER WIRING METHODS ARE INCORRECT. CORD RUN UP INTO CELING THEN PLUGED IN TO LAMP SOCKET. 3.) FURNACE FLUE IS NOT CONNECTED. 4.) SMOKE DETECTORS ARE NEEDED BATTERY OPERATED ARE OK 5.) THE DEAD FRONT COVER IS MISSING ON THE PANEL. 6.) WE HAVE ILLEAGLE SPLICES UNDER THE TRAILER. 7.) THE PEDISTAL IS NOT SET UP FOR A PLUG IN CONNECTION 8.) PLEASE MAINTAIN WORKING CLEARENCES IN FRONT A PEDISTAL 9.) A LICENSED CONTRACTOR WILL BE REQUIRE TO PERFORM THE WORK.
04/15/2002 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection 0000*CANCEL BY OFFICE.