Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2003 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 08/14/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 08/13/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) BOILER CHANCE WITH B.1 VENT - CLEARANCE? 2) BALANCE OF 2ND FLOOR, OK TO COVER. | |
| 07/29/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 07/18/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) MECHANICAL PIPING 100 PSI 2) SECOND FLOOR, AIR HANDLERS, SUSPENDED AND PIPED. PROVIDE ACCESS AS PER 1ST FLOOR | |
| 07/14/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) BASEMENT LAUNDRY ROOM, SHIFT IN BASEMENT/1ST FLOOR, OK. OK TO SEAL | |
| 07/11/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) CONDENSATE PANS-TYPICAL BEDROOM. AIR HANDLERS, OVERFLOW TAKE OFF NOZZLE-OK. ROOM 128-110-109, OK TO COVER | |
| 07/08/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*ENTRY WAY #101- OK TO CLOSE SOFFITT- FIRE DAMPERS- SUPPLY ACCESS OK | |
| 07/03/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) BEDROOMS: PROVIDE SUFFICENT ACCESS TO ELECTRIC. CONTROL PANELS, WATER PIPING ?, STRAINERS AND FUTURE REPLACEMENT AS NECESSARY. BOILER ROOM: CHILLED WATER, HOT WATER. SUPPLY RETURN 100 PSI 2) NEED FIRE DAMPER, POINT OF PENETRATION IN SUPPLY AT ELEVATOR LOBBY | |
| 06/30/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 06/27/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) LAUNDRY ROOM 2) RE-ARRANGE ACCESS PANEL TO EXHAUST BLOWER 3) FIRE DAMPER ACCESS PANELS | |
| 06/25/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) EXHAUST GREASE DUCT WRAP VTR INTO CURL-OK | |
| 06/20/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) BASEMENT, FIRE DAMPERS PROGRESSING OK TO SEAL SOFFIT 2) OK TO BEGIN WRAPING EXHAUST DUCTS TYPE I HOOD | |
| 06/18/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/GRAD SUITE AREA | |
| 06/11/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) ROOM #106 OK TO COVER SOFFIT | |
| 06/05/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) HYDRONIC LINES S. & R. 105 PSI 2) OK TO BEGIN COVERING BASEMENT 3) RECALL FOR CHECK ON FIRE DAMPER PENETRATIONS | |
| 05/13/2003 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection 0999*F.C. 23. PROVIDE ACCESS AS NECESSARY FOR FUTURE REPLACEMENT. RM B15. WHAT ARE TRANSFER GRILLS FOR? WEST DO THEY TRANSFER? IN OR OUT? 2.) ALL FAN COILS. AUX DRAIN PANS? OVERFLOWS? 3.) CHILLED WATER S & R CHILLER INTER MECH. RM., 100 PSI OK. |
|
| 04/28/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*ADDRESSING FINAL LOCATION OF CHILLES PAD WITH APPROVED OF ENGINEER, ARCH., OWNER. BLANK SIDE OF CHILLER IS AGAINST CHAIN LINK FENCE. |