Permit: T02CM00524

Parcel: 11004345C


Addresses:

3275 N SWAN RD

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
12/09/2002 MECHANICAL - HOODS Approved
11/13/2002 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*1.) STRAP FLEX DUCT IN ALL AREAS EVERY 5' 2.) OK FOR CEILING TILES IN PHARMACY. TYPE I EXHAUST FANS WITHIN 10' OF WALL EXTEND. TO TOP OF WALL ALSO B VENTS 2' ABOVE WALL.
3.) PIZZA OVEN IS OK HOOD 4-14 IS OK HOOD D-31 OK. HOOD A 43 CIA IS OK HOLD M 101-A OK. TYPE I EXHAUST FANS WITHIN 10' OF WALL EXTEND TO TOP OF WALL. ALSO B VENTS 2' ABOVE WALL.
11/01/2002 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*OUTLETS ON HOODS DO NOT MEET MIN. CLEARANCE FROM WALK. PROVIDE MIN 6" CLEARANCE. IF YOU WANT TO USE FIRE WRAP HAVE YOUR ENGINEER APPROVE AS SUCH.
09/11/2002 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*INSPECTION WELDS ON GREASE DUCTS. OK TO INSTALL IN SHAFTS.