Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T02CM00524
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2002 | MECHANICAL - HOODS | Approved | ||
11/13/2002 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*1.) STRAP FLEX DUCT IN ALL AREAS EVERY 5' 2.) OK FOR CEILING TILES IN PHARMACY. TYPE I EXHAUST FANS WITHIN 10' OF WALL EXTEND. TO TOP OF WALL ALSO B VENTS 2' ABOVE WALL. 3.) PIZZA OVEN IS OK HOOD 4-14 IS OK HOOD D-31 OK. HOOD A 43 CIA IS OK HOLD M 101-A OK. TYPE I EXHAUST FANS WITHIN 10' OF WALL EXTEND TO TOP OF WALL. ALSO B VENTS 2' ABOVE WALL. |
|
11/01/2002 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*OUTLETS ON HOODS DO NOT MEET MIN. CLEARANCE FROM WALK. PROVIDE MIN 6" CLEARANCE. IF YOU WANT TO USE FIRE WRAP HAVE YOUR ENGINEER APPROVE AS SUCH. | |
09/11/2002 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection 0000*INSPECTION WELDS ON GREASE DUCTS. OK TO INSTALL IN SHAFTS. |