Permit: T02CM00524

Parcel: 11004345C


Addresses:

3275 N SWAN RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
08/26/2002 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
08/23/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*TRAP PRIMER IS REQUIRED FOR FLOOR DRAIN @ OUTDOOR EATING AREA.
08/15/2002 PLUMBING - ROUGH, SOIL Partial Approval 1.) 2" YARD WATER LINE FROM METER TO BACKFLOW PREVENTER AND BLDG. SERVICE IS OK.
08/09/2002 PLUMBING - ROUGH, SOIL Partial Approval 1.) FINAL CONNECTION TO ALL THOUGH DRAINS ARE OK. 2.) OK FOR CONCRETE.
07/17/2002 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1.) GREASE INTERCEPTORS HAVE BEEN INSTALLED 2.) OK TO BACKFILL
06/21/2002 PLUMBING - ROUGH, SOIL Partial Approval 1.) SOIL WATER TEST FOR 4' BLDG DRAIN @ COFFEE SHOP IS OK 2.) WILL REQUIRE A REVISED DRAWING SHOWING 4" BLDG. DRAIN TO COFFEE SHOP. PLBG. CONTRACTOR WILL RED LINE DRAWING ON THIS DRAIN.
06/18/2002 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) THIS INSPECTION IS FOR COMBINATION WASTE & VENT SYSTEM BETWEEN GRID LINE 7.2 THRU 3.) OK NORTH 4. 3.) OK TO BACKFILL TRENCH. 4.) MUST SEE TAIL PIECE AND FLOOR SINKS PRIOR TO CONCRETE.
06/13/2002 PLUMBING - ROUGH, SOIL Partial Approval 1.) SOIL WATER TEST IS OK 2.) THIS INSPECTION IS FOR COMBINATION WASTE & VENT SYSTEM FOR FROZEN FOOD & FLORAL AREA ONLY. 3.) OK TO BACKFILL TRENCH.
06/12/2002 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*NOT READY FOR INSPECTION.
06/10/2002 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) THIS INSPECTION IS FOR ROUGH PLBG. BETWEEN COLUMN D EAST TO H AND GRID LINE #1 SOUTH TO #3 ONLY 3.) ONLY TO BACKFILL TRENCH.
06/07/2002 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) THIS INSPECTION IS FOR U.G. ROUGH PLBG. FOR MEAT DEPT. ONLY 3.) AIR PRESSURE TEST FOR 2" WATER SERVICE BLDG. A SHOPS. 4.) OK TO BACKFILL TRENCH.
06/05/2002 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) THIS INSPECTION IS FOR 4" GREASE LINE ONLY 3.) OK TO BACKFILL TRENCH.
06/04/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) TRAP ARMS FOR 4" TD-1 MUST HAVE MIN DISTANCE FROM CROWN OF TRAP TO BARCEL OF RISER 2 TIMES THE PIPE DIAMETER. 2.) RETEST SYSTEM 3.) AIR PRESSURE TEST FOR 2" C.W. IS OK 2" C.W. IS STUBBED OUT OF BLDG. ONLY.
05/24/2002 PLUMBING - ROUGH, SOIL Partial Approval GROUND PLUMB TO GRID D-10.5.