Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/09/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/06/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) SUPPORT 1/2" CONDUIT IN MEZZ ABOVE PNL 'PA' ALSO 3/4" CONDUIT PER NEC. 2) COMPLETE MAKEUP, COVER 4S BOX IN MESS 3) LABEL DISCONNECTS ON ROOF, AND MEZZ EQUIP 4) SUPPORT J-BOX ON ROOF AT MUA-5 PER 110-22 5) 600V DISCONNECT ON RACK #1 MEZZ IN VIOLATION OF DEDICATED WORKING CLEARANCE 110-26 NEC 6) DISCONNECT FOR GARBAGE COMPACTOR IN VIOLATION OF WORKING CLEARANCE APT 110 NEC 7) INSTALL CIRCUIT PNL SCHEDULES ALL PANELS AND BLANK BREAKER SPACES NOT USED 8) COMPLETE CONNECTIONS TO ALL DELI EQUIPMENT 9) FLEXIBLE LORDS NOT ALLOWED WHERE RUN THROUGH GRID CEILINGS FOR TRACK LTG 400-8 NEC. |
| 11/18/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK TEMP C OF O FOR STOCKING. |