Permit: T02CM00524

Parcel: 11004345C


Addresses:

3275 N SWAN RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM00524

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
11/25/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*T02CM00524
OK WALLS CHILD CAPE CENTER.
11/06/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) PROVIDE LETTER OF TORQUE FOR SWITCH GEAR.
2.) INSTALL INSULATING BUSHINGS ON TERMINATIONS. #4 AWG OR LARGER PER NEC.
3.) TEST RESULTS FOR GFCI MAIN BREAKER IN SWITCH GEAR.
4.) NEMA 3R HOODS FOR TRANSFORMERS OUTSIDE.
5.) NEED APPROVAL OTHER INSPECTORS FOR TEMP POWER.
10/30/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*NOTES 1.) COMPLETE GEAR TERMINATIONS 2.) NEED TO HAVE NEUTRAL BONDED 3.) INSTALLED LABELS 4.) NEED LETTER OF TORQUE FOR GEAR.
10/28/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*COULD NOT LOCATE ELECTRICIAN FOREMAN OR SUPT. FOUND I ELECTRICIAN DID NOT KNOW WHAT NEEDED TO BE INSPECTED. 25MIN. LOOKING.
10/02/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TOWER AT FRONT ENTRY AND SOFFIT FRONT.
09/18/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS.
09/10/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*NOTES OK WALLS BAKERY/DELI AREA AT SOUTH END OF BLD. EXCEPT ABOVE PANEL BOARDS WHERE HOME RUNS NEED TO BE TIED IN.
09/09/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*NOTE COMPLETE SUPPORTING OF CONDUITS COMPLETE CONDUIT INSTALL, SUPPORT WITHIN 3' EACH BOX.
09/04/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK PANEL AND CONDUITS AT IMPACT DOOR.
08/22/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS MEZZ MECH. ROOM
08/09/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
08/07/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) OK WALLS ROOM #138 141 NORTH WALL, 135, 149, EAST WALL. NORTH EAST CORNER OUTER WALL VENDING MACHINE AREA. 2.) PLEASEE TRY TO HAVE AREAS MORE COMPLETE BEFORE CALLING FOR INSP.