Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM00524
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
11/25/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*T02CM00524 OK WALLS CHILD CAPE CENTER. |
|
11/06/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) PROVIDE LETTER OF TORQUE FOR SWITCH GEAR. 2.) INSTALL INSULATING BUSHINGS ON TERMINATIONS. #4 AWG OR LARGER PER NEC. 3.) TEST RESULTS FOR GFCI MAIN BREAKER IN SWITCH GEAR. 4.) NEMA 3R HOODS FOR TRANSFORMERS OUTSIDE. 5.) NEED APPROVAL OTHER INSPECTORS FOR TEMP POWER. |
|
10/30/2002 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*NOTES 1.) COMPLETE GEAR TERMINATIONS 2.) NEED TO HAVE NEUTRAL BONDED 3.) INSTALLED LABELS 4.) NEED LETTER OF TORQUE FOR GEAR. | |
10/28/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0920*COULD NOT LOCATE ELECTRICIAN FOREMAN OR SUPT. FOUND I ELECTRICIAN DID NOT KNOW WHAT NEEDED TO BE INSPECTED. 25MIN. LOOKING. | |
10/02/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TOWER AT FRONT ENTRY AND SOFFIT FRONT. | |
09/18/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK WALLS. | |
09/10/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*NOTES OK WALLS BAKERY/DELI AREA AT SOUTH END OF BLD. EXCEPT ABOVE PANEL BOARDS WHERE HOME RUNS NEED TO BE TIED IN. | |
09/09/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTE COMPLETE SUPPORTING OF CONDUITS COMPLETE CONDUIT INSTALL, SUPPORT WITHIN 3' EACH BOX. | |
09/04/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK PANEL AND CONDUITS AT IMPACT DOOR. | |
08/22/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK WALLS MEZZ MECH. ROOM | |
08/09/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
08/07/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) OK WALLS ROOM #138 141 NORTH WALL, 135, 149, EAST WALL. NORTH EAST CORNER OUTER WALL VENDING MACHINE AREA. 2.) PLEASEE TRY TO HAVE AREAS MORE COMPLETE BEFORE CALLING FOR INSP. |