Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/26/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*/ 1) NOTE: CHECK ADDRESSING FOR THIS UNIT, UNIT ONE BLOCK NORTH IS ADDRESSED 6645??